Extracted from Nittobo Boseki Co. Ltd - 12th August 1991

 

Re: Sound Absorption

Our research Department advises that by adopting method to deepen patterns and to have double processing on the surface of Mineral Fibre Acoustical Ceiling SOLATON ST-721 (Fissured) 15mm the sound absorption rate is believed to achieve following figures:

FREQUENCY............... 125   250   500   1000   2000   4000   NRC
Our catalogue 0.34   0.42   0.53   0.68   0.66   0.63   0.57
Deepen pattern 0.42   0.54   0.63   0.75   0.77   0.74   0.67
Double process 0.49   0.61   0.74   0.77   0.76   0.75   0.72

Laboratory test results also showed remarkable improvement in noise reduction by deepening patterns as well as double processing method. The air space adopted is 300 mm. We are flexible in paying much attention to customers request in various areas not only NRC by also service after installation.

Very truly yours,
 
NITTO BOSEKI CO. LTD.

 

AIRBORNE SOUND ATTENUATION

 

...... .Taken from NATA Report No. 1214-89 .........

 
..................PARTICULARS : .........Determination of the airborne sound attenuation of a ceiling in
.......................................................accordance.with AS2499-1981 (two room method)
..................FOR :...........................Bowmans College
......................................................36 Hotham Parade
............................................ARTARMON NSW 2064
 
........SPECIMEN TESTED :...SOLATON CEILING TILE (ST-725AK)

 

DESCRIPTION OF SPECIMEN :

The ceiling tiles were made of wet felted starch bonded mineral fibre material with thickness of 15mm, length 1186mm and width 400mm. The nominal density of the tile was stated to be 360 kg /m³. Assessment of a single tile sample indicated a density of 390 kg /m³.

INSTALLATION OF SPECIMEN :

The ceiling tiles were fitted tightly into a one way exposed grid system using acess (shiplap) tiles, cut back and kerfed on both long sides, with square cut ends.

Where the ceiling passed over the dividing wall, fibreglass strips were inserted over the dividing wall, which then were sealed into place using a 5mm to 8mm thick layer of plaster applied to both sides of the wall between the ceiling and the top of the wall. The plaster used had one (1) hour curing time.

TEST PROCEDURE :

A wide band random noise generator with pink noise filter was connected to a power amplifier and four (4) "flat" loudspeakers. The loudspeakers were positioned on the two walls and the floor in a corner of the source room remote from the dividing wall to excite the maximum number of room modes as required by clause 3.1 of the Standard.

A single microphone was used in each room to sample the sound field. It was attached to a straight line microphone traversing system which was moved slowly across the major room diagonal. The microphone output was monitored by means of a one third octave band real time spectrum analyser which was configured to provide a linear average over a time period of 128 seconds, during which time the microphone completed one traverse of the room diagonal.

The background noise was measured in the receiving room and the source room's noise spectrum was adjusted by means of a graphic equaliser to ensure that the received sound levels were at least 5dB above the background level in all relevant test frequency bands, as required by clause 2.8 of the Standard. The average receiving and source room noise spectra were then measured without altering the input level or equaliser settings.

OVERALL PRECISION OF RESULTS :

The precision of the measurements has been determined by measurements made at a number of fixed positions equally spaced along the length of the traversing system. The 90% confidence limits are as follows :

+ 2 dB   (125 Hz to 200 Hz)
+ 1.5 dB   (250 Hz to 315 Hz)
+ 1 dB   (400 Hz to 800 Hz)
+ 0.7 dB   (1000 Hz to 5000 Hz)

 

RESULTS :

 

Third Octave Band
Centre Frequency
(Hz)
Average Sound Pressure Level
Difference
(dB)
CAC
43
Deficiencies

(dB)

125 27 27 -
160 31 30 -
200 36 33 -
250 37 36 -
315 33 39 6
400 35 42 7
500 38 43 5
630 39 44 5
800 42 45 3
1000 44 46 2
1250 45 47 2
1600 49 47 -
2000 52 47 -
2500 56 47 -
3150 55 47 -
4000 56 47 -
5000 58 47 -
       
  TOTAL .......30

 

The ceiling attenuation class was (CAC) ................43

 

Note : The results reported above apply only to the specific sample submitted for measurement.
No responsibility is assumed for performance of any other specimen.
 

 

                 
.......
..............
.